Piscataway Campus
732-885-5555
Bensalem Campus
877-726-7663

Diesel Generator Sets

CM20C Generator Set

  • Minimum Rating
    985 kWe
  • Maximum Rating
    1650 kWe
  • Emissions
    (WB) Stage 1 and 2
  • Voltage
    3000 to 13800 Volts
Generator Set Specifications
Minimum Rating
985 kWe
Maximum Rating
1650 kWe
Emissions
(WB) Stage 1 and 2
Voltage
3000 to 13800 Volts
Frequency At Speed
50 Hz @ 1000 / 60 Hz @ 900
Duty Cycle
Prime, Continuous
Ready To Accept Loads
40 s
Normal Ramp Up To 100
75 s
Emergency Ramp Up 10
25 s
Genset Efficiency Up To
43.10%
Engine Specifications
Engine Model
CM20C, 4-stroke-engine
Bore
7.87 in
Stroke
11.81 in
Aspiration
Turbocharged-aftercooled
Engine Rating Range
1020 - 1710 kW
Configuration
6,8,9 cylinder
Fuel Type
Diesel oil / heavy fuel oil (HFO) / crude oil
Swept Volume
575 in³
Mean Effective Pressure Up To
351 psi
Specific Fuel Oil Consumption
0.417 Ib/kWh
Specific Fuel Oil Consumption
0.417 Ib/kWh
Specific Lube Oil Consumption
0.001 Ib/kWh
Generator Set Dimensions
Length
239 in
Length
281 in
Width
66 in
Width
71 in
Height
112 in
Height
119 in
Dry Weight
41447 lb
Dry Weight
66139 lb
  • Fuel System
    • Pre-pressure module
    • Circulation module
    • Separator module
    • Gas valve unit (GVU) (only dual fuel (DF) and gas)
    • Engine ventilation module (only dual fuel (DF) and gas)
    • Ignition fuel oil module (only dual fuel (DF))
  • Lubricating Oil System
    • Combined module: cooling water system and lube oil system
    • Piping interface module
    • Lube oil separator module
  • Cooling Water System
    • Piping interface module
    • Cooling water system with radiators
    • Combined module: see lube oil system
  • Starting System
    • Starting air compressor module
    • Starting air receiver module
  • Combustion Air System
    • Air filter - oil bath
    • Air filter - pulse
    • Air filter - pocket
  • Exhaust System
    • Selective catalytic reduction (SCR) system
    • Oxidation catalytic (Oxicat) converter system
    • Exhaust gas ventilation module (only dual fuel (DF) and gas)
    • Exhaust gas silencer
  • Control & Monitoring System
    • Motor control center module (MCC)
    • Local data panel (LDP) / generator control panel (GCP)
    • Local control panel (LCP)
    • Engine monitoring package
    • Gas leak detection per cylinder (only dual fuel (DF) and gas)
  • Mounting System
    • Elastic mounting - genset/engine