CM25E Generator Set

  • Minimum Rating
    1940 kWe
  • Maximum Rating
    2910 kWe
  • Emissions
    (WB) Cert stage 1 and 2
  • Voltage
    3000 to 13800 Volts
Generator Set Specifications
Minimum Rating
1940 kWe
Maximum Rating
2910 kWe
Emissions
(WB) Cert stage 1 and 2
Voltage
3000 to 13800 Volts
Frequency At Speed
50 Hz @ 750 / 60 Hz @ 720
Duty Cycle
Prime, Continuous
Ready To Accept Loads
40 s
Normal Ramp Up To 100
85 s
Emergency Ramp Up 10
30 s
Genset Efficiency Up To
43.50%
Engine Specifications
Engine Model
CM25, 4-stroke-engine
Bore
10.04 in
Stroke
15.75 in
Aspiration
Turbocharged-aftercooled
Engine Rating Range
2010 - 3015 kW
Configuration
6,8,9 cylinder
Fuel Type
Diesel oil / heavy fuel oil (HFO) / crude oil
Swept Volume
1247 in³
Mean Effective Pressure Up To
396 psi
Specific Fuel Oil Consumption
0.412 Ib/kWh
Specific Fuel Oil Consumption
0.412 Ib/kWh
Specific Lube Oil Consumption
0.001 Ib/kWh
Generator Set Dimensions
Length
304 in
Length
343 in
Width
93 in
Width
93 in
Height
152 in
Height
160 in
Dry Weight
94799 lb
Dry Weight
123459 lb
  • Fuel System
    • Engine ventilation module (only dual fuel (DF) and gas)
    • Ignition fuel oil module (only dual fuel (DF))
    • Separator module
    • Pre-pressure module
    • Circulation module
    • Gas valve unit (GVU) (only dual fuel (DF) and gas)
  • Lubricating Oil System
    • Combined module: cooling water system and lube oil system
    • Lube oil separator module
    • Piping interface module
  • Cooling Water System
    • Piping interface module
    • Combined module: see lube oil system
    • Cooling water system with radiators
  • Starting System
    • Starting air receiver module
    • Starting air compressor module
  • Combustion Air System
    • Air filter - oil bath
    • Air filter - pocket
    • Air filter - pulse
  • Exhaust System
    • Oxidation catalytic (Oxicat) converter system
    • Selective catalytic reduction (SCR) system
    • Exhaust gas ventilation module (only dual fuel (DF) and gas)
    • Exhaust gas silencer
  • Control & Monitoring System
    • Gas leak detection per cylinder (only dual fuel (DF) and gas)
    • Motor control center module (MCC)
    • Local control panel (LCP)
    • Engine monitoring package
    • Local data panel (LDP) / generator control panel (GCP)
  • Mounting System
    • Elastic mounting - genset/engine