Piscataway Campus
732-885-5555
Bensalem Campus
877-726-7663

Diesel Generator Sets

DE110 GC Generator Set (50 Hz)

  • Minimum Rating
    110 kVA
  • Maximum Rating
    110 kVA
  • Emissions
    Non Regulated
  • Voltage
    380 to 415 Volts
Generator Set Specifications
Minimum Rating
110 kVA
Maximum Rating
110 kVA
Emissions
Non Regulated
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby
Engine Specifications
Engine Model
C4.4, In-line 4, 4-cycle diesel
Bore
4.1 in
Stroke
5 in
Displacement
268.5 in
Compression Ratio
18.23:1
Aspiration
Turbocharged Air To Air Charge Cooled
Fuel System
Inline
Governor Type
Mechanical
Generator Set Dimensions
Length
108.1 in
Width
39.3 in
Height
58.1 in
Dry Weight
1330 lb
  • Engine
    • C4.4, Inline 4 Cylinder, 4 Stroke Diesel
  • Genset Control
    • GCCP 1.1
  • Governor
    • Mechanical Governor
  • Fuel Storage
    • Single Wall 8 Hour Tank
  • Alternator
    • A Frame Standard Alternator
  • Enclosure
    • Cat GC Enclosure
  • Air, Cooling & Exhaust
    • Enclosure Silencer
  • General
    • Engine and alternator pre-paint, Caterpillar yellow
  • Certification
    • Certificate of Conformance 13
    • Australia, CIS, Gulf Certification
  • Auxiliary Supply Voltage
    • 120V
  • Alternator Requirements
    • Space Heater
  • Fuel Storage
    • Dual Wall 8 Hour Tank
    • Single Wall Tank With Containment
    • High Fuel Level Alarm
    • Low Fuel Level Alarm
    • Low Fuel Level Shutdown
  • Genset Control
    • Volt Free Contacts for Common Alarm
    • Panel Mounted Audible Alarm
    • Earth Fault
    • Volt Free Contacts for Genset Running
    • Emergency Stop with Key
    • Earth Leakage
    • Battery Charger
    • USB to RS485 Communications Device
    • Coolant Heater
    • Standby Pack (Smart Jacket Water Heater, Battery Charger)
    • Battery
    • Low Coolant Level Shutdown
  • Circuit Breaker
    • 3 Pole Circuit Breaker 125A
    • 3 Pole Circuit Breaker 160A
    • 3 Pole Circuit Breaker 200A
    • 4 Pole Circuit Breaker 125A
    • 3 Pole Circuit Breaker 400A
    • 3 Pole Circuit Breaker 250A
    • 4 Pole Circuit Breaker 160A
    • 4 Pole Circuit Breaker 250A
    • 4 Pole Circuit Breaker 200A
    • Circuit Breaker Padlock
    • 4 Pole Circuit Breaker 400A
    • Neutral Earth Link
    • Overload via Alarm Switch on Breaker
  • Testing & Packaging
    • PGS Test Report @ 1.0PF
    • PGS Test Report @ 0.8PF