Piscataway Campus
732-885-5555
Bensalem Campus
877-726-7663

Electric Power Generation

XQP100

  • Rating
    100 kVA Prime
  • Rating Prime
    100 kVA
  • Frequency
    50/60 Hz
  • Voltage
    127 - 480 V
Generator
Rating
100 kVA Prime
Rating Prime
100 kVA
Frequency
50/60 Hz
Voltage
127 - 480 V
Prime Power
6.2 gal/hr
IPP Rated 60Hz
77.5 dB(A)
Engine
Engine
C4.4 Diesel Engine or Cat C4.4 ACERT Diesel Engine
Fuel
Diesel
Dimensions
Width
44.1 in
Height
72.7 in
Length
109.1 in
Weight
4469 lb
Fuel Consumption EU Stage IIIA
100
6.2 gal/hr
100
7.3 gal/hr
100
7.3 gal/hr
75
5.4 gal/hr
75
5.4 gal/hr
75
5.9 gal/hr
75
5.9 gal/hr
50
3.9 gal/hr
50
3.9 gal/hr
50
4.2 gal/hr
50
4.2 gal/hr
Fuel consumption Best Fuel Efficiency
100
6 gal/hr
100
6 gal/hr
100
7.1 gal/hr
100
7.1 gal/hr
75
4.5 gal/hr
75
4.5 gal/hr
75
5.3 gal/hr
75
5.3 gal/hr
50
3.1 gal/hr
50
3.1 gal/hr
50
3.7 gal/hr
50
3.7 gal/hr
Noise rating (with enclosure) EU Stage IIIA
Sound Power
77.5 dB(A)
Sound Power
79.5 dB(A)
Sound Power
79.5 dB(A)
Noise rating (with enclosure) Best Fuel Efficiency
Sound Power
80.3 dB(A)
Sound Power
80.3 dB(A)
Sound Power
81.6 dB(A)
Sound Power
81.6 dB(A)
Fuel Consumption Prime
100
  • CAT C4.4 Diesel Engine
    • Turbo charged.
  • Generator
    • LC3114F frame.
  • Air Filter
    • Cyclonic/paper with dust cup and service indicator.
  • Cat Connect remote monitoring
    • Provides package monitoring and management.
  • Cooling System
    • Package mounted radiator with vertical air discharge. Filled from factory.
  • Charging / Starting System
    • 12V heavy duty starting motor and charging alternator c/w battery isolator.
  • Fuel System
    • 24hr dual wall fuel tank with 3 way directional valve for external supply.
  • Control Panel
    • Digital EMCP4.2B set mounted controller.
  • Distribution
    • Single, robust enclosure for controls and distribution c/w 4 pole circuit breaker and safety cut off.
  • Structure
    • Heavy Duty steel base frame with integral fuel tank. Fork lift pockets. Dragging bars. Lifting frame and 4 point lift. Base frame is wider than enclosure to protect generator set during transportation.
  • Enclosure
    • Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance.
  • Exhaust
    • Integrated spark arresting silencer.
  • Lube Oil
    • On engine primary and secondary oil filters. Filled from factory.
  • General
    • Factory tested and inspected.