Diesel Generator Sets
D550 GC (60 Hz) Generator Set
-
Maximum Rating550 ekW
-
Minimum Rating550 ekW
-
EmissionsEPA Stationary Emergency
-
Voltage480 to 600 Volts
Generator Set Specifications
- Maximum Rating
- 550 ekW
- Minimum Rating
- 550 ekW
- Emissions
- EPA Stationary Emergency
- Voltage
- 480 to 600 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby
Engine Specifications
- Engine Model
- Cat® C18 In-line 6, 4-cycle diesel
- Bore
- 5.7 in
- Stroke
- 7.2 in
- Displacement
- 1106 in³
- Compression Ratio
- 14.5:1
- Aspiration
- Turbocharged Air-to-Air Aftercooled
- Fuel System
- MEUI
- Governor Type
- ADEM™A4
Generator Set Dimensions
- Length
- 196.1 in
- Width
- 73.4 in
- Height
- 79.1 in
- Height
- 100.9 in
- Dry Weight
- 8776.6 lb
- Dry Weight
- 11464 lb
-
Air Inlet System
- Air cleaner - Non-Canister, Disposable
- Aftercooler core
- Turbocharger
-
Control Panel
- GCCP 1.2
-
Cooling System
- Jacket water pump, gear driven, centrifugal
- Radiator, Package mounted.
- Radiator sight gauge
- Thermostats and housing.
- Blower fan and fan drive with guards
- Coolant drain valve.
-
Exhaust System
- Exhaust manifold; dry
-
Fuel System
- Fuel priming pump
- Primary fuel filter w/integral water separator and secondary filter, spin on
- Engine fuel transfer pump
- Fuel cooler
- Integral Tank Base, 24 Hrs, UL142
-
Generator Set
- Complete system designed & built at ISO 9001:2000 certified facilities
- All protective devices and control functions simulated and checked
- Factory tested to design specifications at full load conditions
-
Generators and Generator Attachments
- Insulation, Class H
- Standard winding protection for non-harsh environments with relative humidity ? 95%
- Terminal Box, IP22 RHS Facing, Bottom Cable Entry
- IP23 protection
- 6 leads
- Voltage regulator (single phase sensing)
- Easy access to AVR and terminals
- Brushless, self-excited 2/3 pitch (600V uses Internal Excitation)
-
Governing System
- Cat Electronic Governor (ADEM A4)
-
Lube System
- Lubricating Oil, CK-4 (10W-30)
- Oil cooler
- Oil drain with valve.
- Shallow oil pan.
- Oil filter, spin on.
- Fumes disposal to front of radiator.
- Oil filler and dipstick.
-
Mounting System
- Captive linear vibration isolators between base and engine-generator
- Includes lifting provisions and termination points for coolant and lube oil drain lines
-
Protection
- Safety Shutoff - Overspeed
- Safety Shutoff - Low Oil Pressure
- Safety Shutoff - High water temperature
-
Starting/Charging System
- 24-volt electric starting motor.
- 24V,45 amp charging alternator.
-
General
- Lifting Eyes
- Parts Book
- Vibration damper.
-
Air Inlet System
- Air Cleaner (Non-Canister Disposable)
-
Bases, Mounting & Fuel Tanks
- Integral Tank Base, 24 Hrs, UL142
- Fuel Tank Fill Pipe & Lockable Cap
- Audio & Visual Fuel Alarm (@90% Fuel Level)
- 5 gallon Spill Containment
- Overfill Prevention Valve
- Wide Base - Skid
-
Circuit Breaker
- 400A LS/I
- 1200A LS/I
- Auxiliary Contacts
- 800A LSI
- 800A LS/I
- 600A LSI
- 600A LS/I
- 400A LSI
- 1200A LSI
-
Control System
- Volt Free Contacts
- 20A GFCI (Ground Fault Circuit Interrupter)
- 16 -light NFPA 99/110 Annunciator
- Twist Release, Red Button Emergency Stop
- Product Link Remote Monitoring hardware
- 100A Load Center
- Ground Fault Relay
- Audible Alarm Gp
- Annunciators box
- Remote E-Stop button
- Local annunciator
- Discrete I/O module
- Volt free contact
- Earth (Ground) fault relay
-
Enclosures
- Sound Attenuated Level 2 Enclosure (White)
- AC & DC Source Lights
- E-Stop
- Sound attenuated enclosure
-
Exhaust System
- Flexible Exhaust Connection
- Manifold & Turbocharger Guards
- 8" Muffler - 25 dBA Attenuation
-
Generator
- Space Heater
- Permanent Magnet Generator
-
Starting System
- Standard Battery Set: 1000 CCA, 90 amp/hr.
- Battery Charger (UL Certified)
- Jacket Water Heater
- Oversize Battery Set, 1400 CCA, 200 amp/hr.
-
General
- CSA Certification
- Extended Service Coverage
- UL2200 Certification
- Generator Test Report
- Tool set
-
Circuit Breakers
- Single LSI motorised circuit breaker
- Auxiliary contacts
- Neutral bar (208V)
-
Cooling System
- Jacket water heater with pump
- Coolant heater
- Stone guards
-
Base / Fuel Tank
- Audio & visual fuel alarm
-
Fuel System
- Integral 8 hr tank base
-
Starting and Charging
- Oversize battery set
- Battery disconnect switch
- 5 Amp battery charger
- Standard battery set
-
Certifications
- UL2200 Listed
- CSA 22.2
- Seismic
-
Lube System
- Manual sump pump