Piscataway Campus
732-885-5555
Bensalem Campus
877-726-7663

Diesel Generator Sets

DE50E0 (50 Hz) Generator Set

  • Minimum Rating
    50.0 kVA
  • Maximum Rating
    50.0 kVA
  • Emissions
    Non Regulated
  • Voltage
    220 to 415 Volts
Generator Set Specifications
Minimum Rating
50.0 kVA
Maximum Rating
50.0 kVA
Emissions
Non Regulated
Voltage
220 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby
Engine Specifications
Engine Model
Cat® C3.3
Bore
4.1 in
Stroke
5 in
Displacement
201.4 in³
Compression Ratio
17.25:1
Aspiration
Turbocharged
Fuel System
Inline
Governor Type
Mechanical
Generator Set Dimensions
Length
75.8 in
Width
44.1 in
Height
53.6 in
Dry Weight
1891 lb
  • Control panel
    • GCCP Control panel
  • Alternator and Alternator attachments
    • 12 Leads
    • IP23 Protection
    • Voltage regulator (single phase sensing)
    • Tower panel, IP22, bottom cable entry
    • Segregated low voltage (AC/DC) wiring panel
    • Circuit breaker, IEC, 3 Pole, mounted in tower panel
  • Governing system
    • Mechanical governor
  • Cooling system
    • Radiator and cooling fan with guards
    • Coolant drain line with valve
    • Fan drive, battery charging alternator drive
    • Caterpillar extended life coolant
  • Air inlet system
    • Air cleaner; light duty with disposable element
  • Exhaust system
    • Stub pipe, gaskets, raincap & SAE exhaust flange
    • Industrial silencer
  • Fuel system
    • Standard open set fuel tank/base
  • Lube system
    • Lubricating oil
    • Oil drain line with valve
  • Mounting system
    • Captive linear vibration isolators
    • Lifting provision and drag points
    • Termination points for coolant and lube oil drain lines
  • Starting/charging system
    • 12V Battery with rack & cables
  • General
    • Engine and alternator pre-paint, Caterpillar yellow
  • Control panel
    • GCCP Control panel
    • Earth fault and earth leakage
    • Emergency E-Stop with security key
    • 4 Pole Circuit breaker
    • Voltage and speed adjust potentiometer
  • Alternator and Alternator Attachments
    • LC Frame alternator
    • LC/M Frame alternator
    • Space heater
    • Permanent magnet excitation (PMG)
    • Automatic voltage regulator
  • Enclosures
    • Level 1 and Level 2 sound attenuated enclosures
    • Single point lifting frame
    • Rental pack
    • SBOX - CEE form sockets
  • Alarms and Shutdowns
    • Common alarm
    • Overload shutdown
    • Low coolant level shutdown
    • Low coolant temperature alarm
    • Low fuel level alarm and shutdown
    • High fuel level alarm
  • Engine
    • Electronic governor
    • Jacket water heater
    • Battery charger
  • Fuel system
    • Bunded base tank sized for a minimum of 12 hours running with 110% spill protection
  • Exhaust system
    • Residential silencer 25 dBA
  • Certification
    • Certificate of Conformance
    • EAC Certification
  • Extended service coverage
    • 3, 4, 5 and 10 Years