3412C | 750kVA 50Hz Generator Set

Exterior View

3412C | 750kVA 50Hz Generator Set

Maximum Rating750 kVA
Minimum Rating680 kVA
Emissions/Fuel StrategyLow Fuel Consumption
Voltage380 to 415 Volts
product-tabs-bg

Learn more about our 3412C | 750kVA 50Hz Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Maximum Rating
750 kVA
Minimum Rating
680 kVA
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime
Engine Model
3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.4in
Stroke
6in
Displacement
1648.86in³
Compression Ratio
13:01
Aspiration
Turbocharged, Air to Air Aftercooled
Fuel System
Pump and Lines
Governor Type
™ A5" data-metric=""> ADEM A5
Length - Maximum
162.4in
Width - Minimum
75in
Width - Maximum
78.3in
Height - Maximum
75in
Dry Weight - Genset (minimum)
12039lb
Dry Weight - Genset (maximum)
13030lb
Air cleaner, single element canister type with service indicator
GCCP Control panel
Over/under voltage (27 / 59)
Environmental sealed front face
Generator phase sequence
Communications
Digital I/O module
Features include:
2 Programmable relay outputs (Form C)
Compatible with the following optional modules:
Customer data link (Modbus RTU)
4 programmable relay outputs (Form A)
Amps (per phase & average)
kVA (per phase, average & percent)
Text alarm/event descriptions
Low coolant level
Generator temperature monitoring module
Run/auto/ stop/control
Overspeed
Serial annunciator module data link
Emergency stop pushbutton
Frequency (Hz)
RPM
6 programmable digital inputs
Oil pressure (psi, kPa or bar)
Engine cycle crank
Operating hours
Local annunciator
coolant temperature
kW-hr (total)
Programmable protective relaying functions:
kW (per phase, average & percent)
Low oil pressure
Reverse power (kW) (32)
Remote Serial annunciator
DC volts
Power factor (per phase & average)
Remote CAN annunciator
24 Volt DC operation
Accessory module data link
Failure to start (overcrank)
Over/under frequency (81 o/u)
kVAr (per phase, average & percent)
Warning/shutdown with common LED indication of shutdowns for:
Low coolant temperature
2 Programmable digital outputs
Reverse reactive power (kVAr) (32RV)
Emergency stop
Digital indication for:
High coolant temperature
Speed adjust
Voltage adjust
Volts (L-L & L-N)
Overcurrent (50 / 51)
Fan and belt guards
Coolant drain line with valve, piped to edge of base
Caterpillar extended life coolant
Coolant level shutdown
Radiator with guard (Sized for 50 degrees C)
Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose
Flexible fuel lines terminated on base
Fuel priming pump
Primary and Secondary fuel filters
Water seperator
3-phase sensing
SR4B self excited
Class H insulation
2:1 Volts/Hz
Reactive droop
VR6 voltage regulator
Busbar termination
Class F temperature rise
12 Leads
Cat electronic governor
Oil drain line with valve, piped to edge of base
Lubricating oil
Oil filter
Fumes disposal, piped to front of radiator
Base, formed steel with linear vibration isolators between base and engine-generator
Battery with rack, cables
45 amp Charging alternator
24 volt starting motor
Fuel shutoff solenoid
Open element air cleaners
Heavy duty air cleaners
Dual element air cleaners
1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
First local annunicators
Local discrete I/O package
Generator temperature monitoring package
Ground fault relay
Remote custom annunicator
GCCP Control panel
Generator running VFC
GCCP Control panel
Vandal proof panel door
Common alarm/shutdown relay
Jacket water heaters
Radiator duct flange
Eurasian Conformity (EAC) mark
Elbow kit
Manifold and turbocharger guards
Through wall installation kit
Mufflers
Digital voltage regulator
Oversize and premium generators
Space heater
Permanent magnet excitation (PMG)
Manual sump pump
Fuel tank base (1200 ltr)
PGS Test report @ 1.0 power factor
PGS Test report @ 0.8 power factor
Heavy duty starting system
Battery chargers
Battery disconnect switch
Oversize batteries
Electronic load share
TO TOP