D80 GC Generator Set

Exterior View
Exterior View
Interior View

D80 GC Generator Set

Maximum Rating80 ekW
Minimum Rating80 ekW
Emissions/Fuel StrategyU.S. EPA Cert., Tier 3
Voltage208 to 600 Volts
product-tabs-bg

Learn more about our D80 GC Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Maximum Rating
80 ekW
Minimum Rating
80 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 3
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby
Engine Model
C4.4, In-line 4, 4-cycle diesel
Bore
4.1in
Stroke
5in
Displacement
269in³
Compression Ratio
16.7:1
Aspiration
Turbocharged
Fuel System
Common Rail
Governor Type
™A4" data-metric=""> Mechanical, ADEMA4
Length - Maximum
82.6in
Width - Maximum
43.3in
Height - Maximum
52.9in
Dry Weight - Genset (maximum)
950lb
Air cleaner; light duty with disposable element
Air cleaner
Radiator and cooling fan with guards
Fan drive, battery charging alternator drive
Caterpillar extended life coolant
Coolant drain line with valve
GCCP 1.2 Control panel
Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
Circuit breaker, IEC, 3 pole, mounted in tower panel
Voltage regulator (single phase sensing)
IP23 Protection
Segregated low voltage (AC/DC) wiring panel
12 Leads
Tower panel, IP22, bottom cable entry
Mechanical and electrical governing system - model dependent
Lubricating oil
Oil drain line with valve
Includes lifting provision and drag points
Termination points for coolant and lube oil drain lines
Captive linear vibration isolators between base and engine-generator
Batteries
24V battery with rack and cables
Engine and alternator pre-paint, Caterpillar yellow
3 Phase sensing
Anti-condensation heater
R Frame auxilliary winding
Permanent magnet excitation (PMG)
Circuit breaker upgrades - 4 Pole circuit reaker to 250A, 400A and 630 A
Low coolant level shutdown
Coolant heater
Low coolant temperature alarm
Earth fault (2 wire only)
Overload shutdown via breaker
Earth leakage (2 wire only)
Volt free contacts
Panel mounted audible alarm
Battery charger
GCCP 1.2 Control panel
Control panel heater
Voltage adjust potentiometer
Emergency stop with key
Speed adjust potentiometer
Sound attenuated Level 2 enclosure
High fuel level alarm
Open set narrow tankbase
Low fuel level alarm
Bunded fuel tank
Low fuel level shutdown
Compact skidbase for open set
Skidbase for CALG enclosure sets
Certification for CIS
Battery removal
Industrial silencer
Electronic governor
External single point lift - enclosure
Silencer installation kit
PGS Test report @ 1.0 power factor
PGS Test report @ 0.8 power factor
Stone guards/rad trans flange
Packing case - canopied set
Packing case - compact set
TO TOP