D150 GC Generator Set

Exterior View
Interior View

D150 GC Generator Set

Maximum Rating150 ekW
Minimum Rating150 ekW
Emissions/Fuel StrategyU.S. EPA Cert., Tier 3
Voltage208 to 600 Volts
product-tabs-bg

Learn more about our D150 GC Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Maximum Rating
150 ekW
Minimum Rating
150 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 3
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby
Engine Model
C7.1 I-6, 4-Cycle Diesel
Bore
4.1in
Stroke
5.31in
Displacement
428in³
Compression Ratio
16.7:1
Aspiration
Turbocharged, Air to Air Aftercooled
Fuel System
Electronic, Common Rail
Governor Type
™A4" data-metric=""> ADEMA4
Length - Maximum
103.7in
Width - Maximum
51.2in
Height - Maximum
52.2in
Dry Weight - Genset (maximum)
3443lb
Air cleaner; light duty with disposable element
GCCP 1.2 Control panel
Fan drive, battery charging alternator drive
Radiator and cooling fan with guards
Coolant drain line with valves
Caterpillar extended life coolant
12 Leads
Segregated low voltage (AC/DC) wiring panel
IP23 Protection
Tower panel, IP22, bottom cable entry
Voltage regulator (single phase sensing)
Circuit breaker, IEC, 3 pole, mounted in tower panel
Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
Standard open set fuel tank/base supplied
Base, formed steel with single wall integral 24-hour fuel tank
Lubricating oil
Oil drain line with valve
Termination points for coolant and lube oil drain lines
Captive linear vibration isolators between base and engine-generator
Includes lifting provision and drag points
24V battery with rack and cables
Mechanical and electrical governing system - model dependent
Engine and alternator pre-paint, Caterpillar yellow
R Frame auxiliary winding: R2273L4 SE aux alt 07, aux alt 08 and aux alt 10
Anti-condensation heater
3 Phase sensing
Quatrature droop king
Alternator removal
Permanent magnet excitation (PMG)
Padlockable breaker device
4 Pole 250A, 400A and 630A Circuit breakers
Battery charger
Panel mounted audible alarm
Emergency stop with key
Speed adjust potentiometer
Control panel heater
Earth leakage (2 wire only)
Earth fault (2 wire only)
Speed adjust contacts
Overload shutdown via breaker
Volt free contacts
Volt free contacts for common alarm
Static battery charger
Volt free contacts for generator set running
Coolant heater
Low coolant level shutdown
Low coolant temperature
Sound attenuated level 2 enclosure
Electronic governor
Residential silencer
Industrial silencer removal
Silencer installation kit
Battery removal
High fuel level alarm
Skidbase for CALG enclosure sets
Compact skidbase for open sets
Open set narrow tankbase
Low fuel level alarm
DEFRA bunded fuel tank
Low fuel level shutdown
PGS Test report @ 1.0 power factor
PGS Test report @ 0.8 power factor
Stone guards/radiator trans flange
Circuit breaker, IEC, 4 pole
Packing case - canopied set
Packing case - compact set
TO TOP