Cat® CG – ATS for general purpose applications

masthead-innerpage-bg

Cat® CG – ATS for general purpose applications

Rating Range30 – 3000 A
Transfer TypeOpen Transition (CG), Delayed Transition (CGD)
Switch TypeContactor
Product nodes30, 60, 100, 125, 160, 200, 260, 400, 600, 800, 1000, 1200, 1600, 2000, 2600, 3000A
product-tabs-bg

Learn more about our Cat® CG – ATS for general purpose applications

The CG Series – Contactor-type, Open Transition (CG) and Delayed Transition (CGD) ATS for general purpose applications offers functionality for critical emergency power applications in commercial and light industrial applications, with an enhanced feature set and LCD HMI interface.

The CG provides a durable mechanism that is tested up to 6,000 cycles. Electrical system parameters are set via the HMI and pre-configuration file upload is available via USB or Bluetooth connection.

Rating Range
30 - 3000 A
Transfer Type
Open Transition (CG), Delayed Transition (CGD)
Switch Type
Contactor
Product nodes
30, 60, 100, 125, 160, 200, 260, 400, 600, 800, 1000, 1200, 1600, 2000, 2600, 3000A
Rated Voltage and Frequency
200-480VAC, 50/60 Hz
Phase system
Single and Three (three phase only >600A)
Number of poles
2, 3 and 4 (3 & 4 pole only >600A)
Neutral configuration
Optional Solid or Switched neutral
Product type
Open transition (I-II), Delayed Transition (I-O-II)
LCD + keys
Voltage and frequency settings: Pick up and Drop out
Time Delay Settings: Override momentary, Transfer, Generator stop, Center-OFF, Pre-transfer, Post-transfer, Elevator Pre-signal, Elevator Post-signal, and Load shead
Source failure detections: No Voltage, Under/Over Voltage, Phase missing, Voltage unbalance, Invalid frequency, and Incorrect phase sequence
LED indications for ATS, S1 and S2 status
Open transition - Standard digital inputs/outputs (1/1)
Delayed transition - Standard digital inputs/outputs (2/1)
Programmable digital inputs/outputs
Auto config (voltage, frequency, phase system)
Source priority (Source 1/2, No priority)
Manual re-transfer
In-phase monitor (synchro check)
Genset exercising: on-load, off-load
Load shedding
Real time clock
Event log
Auxiliary contacts for position indication
Additional digital input/output contacts (adding up to 6 each)
12-24 VDC aux supply module for controller
Communication modules
Modbus RTU (RS-485)
Modbus/TCP
Profibus DP
ProfiNet Yes
DeviceNet
Ethernet IP